| Model | GTYQ-AT0502 |
| Measuring gas | Combustible gases (Methane, propane, isobutane, hydrogen, etc.) |
| Measuring type | Diffusion type |
| Measuring method | Catalytic |
| Measuring Range | 0-100% LEL |
| Response time | < 15sec / 90% scale |
| Accuracy | ±3% / Full Scale |
| Operation mode display | Alarm / Trouble LED |
| Power | 24V DC nominal, 18 to 31V DC |
| Alarm signal output | Light and sound output / 50mA |
| Output signal | XBUS 2/4 wire or HBUS 4 wire |
| Conduit connection | Standard: 2xM26x1.5P Option: FPT3/4',NPT3/4'' |
| Mounting type | Wall/Pole/Ceiling mount |
| Operating temperature | -40°C ~ +70°C |
| Operating humidity | 5 to 95% RH (Non-condensing) |
| Housing Material | Aluminum alloy |
| Dimensions | 146(W) x 144.5(H) x 70.5(D) mm |
| Explosion Proof | Ex db IIC T6 Gb |
| Certification | Refer to website |
| Sensor Type | Measuring Gas | Measuring Range | Operating Temperature | Typical Life | Response Time |
|---|---|---|---|---|---|
| Catalytic Type | Combustible gases | 0~100%LEL | -40+70℃ | 36 month | <15sec / 90% scale |
Output signal shows a good linear relationship with gas concentration, enabling precise concentration readings.
Minimal performance fluctuations during long-term use, ensuring reliable detection results.
Quickly captures gas concentration changes and triggers timely alerts.
Detects most flammable gases and flammable vapors (e.g., hydrogen (H₂), methane (CH₄), propane (C₃H₈), ethanol vapors, etc.).
Exhibits certain tolerance to common poisoning substances (e.g., silicon, lead compounds), with a long service life and low attrition rate.
The GTYQ-AT0502 is fully certified to meet strict industrial safety standards with an Ex db IIC T6 Gb rating, making it suitable for secure flammable gas monitoring in explosive and dust-heavy atmospheres.
No, the digital sensor component of this model is designed for direct replacement on-site without field calibration, which significantly minimizes maintenance difficulty and limits system downtime.
It features a broad-spectrum capability designed to detect most flammable gases and vapors, including methane (CH₄), propane (C₃H₈), hydrogen (H₂), isobutane, and ethanol vapors.
The detector has an IP66 ingress protection rating and operates reliably in temperatures ranging from -40°C to +70°C, rendering it highly durable in harsh indoor and outdoor conditions featuring severe dust and water spray.
Yes, the GTYQ-AT0502 is compatible with both XBUS 2-wire/4-wire and HBUS 4-wire systems, making it a flexible and convenient option for retrofitting projects and old system upgrades.
The catalytic type sensor features a typical service life of 36 months and a quick response time of less than 15 seconds (to reach 90% scale).